Manual

Optimation, Inc.
(256)883-3050 19
www.optimate.com
OptiLogic Series
OL2205 AC/DC Input Module
Inputs 4
Card Cage Power
Required
60mA
Input Type AC Optocoupled Status Indicators Logic Side LED
Voltage Range 10-30 V AC or DC Input Impedence 2.7K
Min. On Current (per
point)
3.3 mA Inputs
DC sinking or sourcing
/ or AC
Max. On Current (per
point)
11 mA Terminal Strip Plug In (removable)
Terminal Screws
Slotted (0.1 blade
max.)
Max. Terminal wire
gauge
18 AWG (use copper
conductors)
Required Temperature
rating of field installed
conductors
60C/75C
Weight 1.2 oz (34g) Terminal block torque 2.2 lb-in
Type 5 Subtype 1
The OL2205 Digital Input module senses up to four (4) AC or DC input signals. All inputs are individually
optocoupled for isolation. Inputs are also individually isolated from each other by separate terminal connections.
Filtering is provided for zero crossover. Individual LED indicators provide visual feedback of current status.
Terminal Terminal
1 In 0 5 In 2
2 In 0 6 In 2
3 In 1 7 In 3
1
2
4
5
6
7
8
3
0
2
3
1
L
OO
2205
I
N
module internal
circuit
optical
isolation
To
OptiLogic
processor
8
7
6
5
4
3
2
1
10-30V AC or DC
IN0
IN1
IN2
IN3