User Guide
Table Of Contents
OEM Design-in Guide
Luxon IoT Node Outdoor
15
Sensor interface output requirements
1: Is case of an open collector output or potential free relay low current contact.
Figure 1: Sensor output switching to 0V. Figure 2: Sensor output switching to 12 to 24Vdc
Maximum IoT node current: 2mA max.
2: In case of an analog 0-10V sensor output voltage.
- Maximum Luxon IoT node sensor input voltage: +28Vdc
- Input resistance Luxon IoT node sensor input: 20kΩ
Safety notes
If the sensor is supplied from mains directly, the sensor signal output shall be SELV or Basic isolated.
Released compatible sensors
For an overview of compatible sensors and wiring diagrams and settings, please refer to portal.nedap-luxon.com.
When you are using other sensors we recommend a final compatibility check by Nedap Light Controls with a sample