Release Notes

10 Express5800/320Lb System Release Notes
When this status appears, follow the steps show below and restore the proper
status.
1) Start the [Start]-[Administrative Tools]-[Services].
2) Right-click on the Stratus ftServer Storage Manager, and execute Restart.
Note: This caution applies only to 320Lc/Lc-R with
Rapid Disk Resync.
11. Cautions for the system booted
In a very rare case, the duplications of the CPU/PCI modules stop when the
server which “ft control software Ver.3.0 Update module No.001 FD” is not
applied is started.
Usually, it is recovered automatically at stop of the duplications because the
update module for this phenomenon is applicable when the server is set up
Event logs 1,2,3 are registered.
Please recover after applying the update module referring to “Procedure to
recover” because the system becomes the following in case of un-application.
<Status of the duplications stopped>
-Status of Status LED
Module Status LEDs(1 and 2)
PCI module Group 1 Green / Red
PCI module Group 2 Green / Red
CPU module 1 off / Amber
CPU module 2 Red / off
Note: If the duplication stops when the system is
rebooted, the status LED (1 and 2) of both CPU modules will
be off / Green.
Please check the following information also, as the LED status show above may
vary depending on when the duplication stops.
-Event log
Start [Start]-[Administrative Tools]-[Event Viewer], and select the system in
the left pane, and confirm that the following logs are registered.
1. Event Source: Service Control Manager
Event ID: 7022