User's Guide
2-14 General Description
On-screen message Description Action
Proc1ThermalTrip Forced power-off occurred due to
a thermal error in CPU#1.
Check if the fans in the Blade
Enclosure work normally.
Check the heat sink of the CPU
blade.
Refer to the User’s Guide of the
Blade Enclosure to make sure that
a sufficient number of fans are
installed.
Check if the fans and CPU blades
are installed in the correct locations.
Check if the ambient temperature of
the installation location satisfies the
operating conditions.
Proc2ThermalTrip Forced power-off occurred due to
a thermal error in CPU#2.
Proc1 Therm % 09 A high temperature error was
detected in CPU#1.
Proc2 Therm % 09 A high temperature error was
detected in CPU#2.
AmbientTempAlm09 A high temperature error was
detected in CPU unit.
DAS AirTempAlm09 A high temperature error was
detected in storage unit.
AmbientTempAlm02 A low temperature error was
detected in CPU unit.
Check if the ambient temperature of
the installation location satisfies the
operating conditions.
DAS AirTempAlm02 A low temperature error was
detected in storage unit.
Battery Alm XX A battery voltage alarm was
detected.
XX=09: Upper limit alarm
XX=02: Lower limit alarm
1. Check the installation status of
the battery.
2. Replace the battery.
Proc1 Vccp AlmXX
Proc2 Vccp AlmXX
BB FSBvtt Alm XX
BB DIMMvtt AlmXX
BB +1.2v Alm XX
BB +1.5v Alm XX
BB +3.3v Alm XX
BB +5v Alm XX
BB +1.2vs Alm XX
BB +1.5vs Alm XX
BB +1.25vs AlmXX
BB +3.3vs Alm XX
BB +5vs Alm XX
BB +12vs Alm XX
A voltage alarm on CPU unit was
detected.
XX=09: Upper limit alarm
XX=02: Lower limit alarm
Replace the CPU blade.