user manual
ND-45504 (E) CHAPTER 4
Page 47
Revision 2.0
PZ-PW86-A (PWR)
(3) Switch Settings
The figure in the SWITCH NAME column and the position in in the SETTING POSITION col-
umn indicate the standard setting of the switch. When the switch is not set as shown by the figure and
, the setting of the switch varies with the system concerned.
Switch Settings
SWITCH NAME
SWITCH
NUMBER
SETTING
POSITION
FUNCTION CHECK
SW102
PRESS
MOMENTARILY
To start each PIM on battery power, when AC
power is not provided (Switch “SW” must be
ON).
1 Set to ON.
2
ON For float charging
OFF
Standard setting for equalize charging (Set to
equalize for Gel cell or no battery.)
SW
ON For turning AC source power on
OFF For turning AC source power off
100/120
240
AC INPUT: 90 V - 138 V
DOWN AC INPUT: 180 V - 276 V
CAUTION
• When the operating power is being supplied to this circuit card, do not plug/unplug this circuit card into/from
its mounting slot.
• Set the appropriate voltage by using the AC voltage select switch (slide switch) before powering on.
1
2
ON
ON
I (ON)
O (OFF)
UP