User Manual Chapter 3
3-4 Chapter 3: Installing the Hardware Infrastructure
• The minimum distances between a communication cable and
electrical equipment/associated power cables are as follows:
Maximum Rated
Circuit Power
Unshielded Power
Cables
Shielded Power
Cables
1 kVA
30.5 cm (14 in.)
2.54 cm (1 in.)
2 kVA
45.7 cm (18 in.)
5.08 cm (2 in.)
5 kVA
60.9 cm (24 in.)
15.24 cm (6 in.)
Over 5 kVA
152.4 cm (60 in.)
30.48 cm (12 in.)
• All interconnecting wiring between the Ethernet hub, CBSs, and
power supplies is low voltage wiring. This wiring must conform to
all local and national electrical codes for the routing of commercial
signal wire.
• Do not route communication cables outside the building.
Tools and Supplies
DecisioNet infrastructure installers must have access to the tools
typically found in an electrician's tool box. Additional tools and
supplies an installation team may require are shown in the following
table.
Tool/Supply
Quantity
Cable ties
10 per CBS
RJ45 Modular Jacks
2 per cable plus spares
Ideal Modular RJ45 crimp kit
1
Milwaukee 2.4 V low-torque electric screw
driver
1
ESL removal tool
1 per installer
Lift truck
1
Ideal LinkMaster CAT5 cable tester
Ideal Cat. No. 62-200
1