Product Manual
Page 10
appropriate crimping tools are required. Please check on website www.andersonpower.com under
the Powerpole Connectors section for parts details and the wire crimping methods.
PP45 Red Connector Housing & 45 amp Contact (1 pc): P/N 1345
PP45 White Connector Housing & 45 amp Contact (1 pc): P/N 1345G7
The red connector is used to connect to the positive terminal of the Solar Home and RV Kit and
the white connector is used to connect to the negative (ground) terminal of the Solar Home and
RV kit system.
Add pictures of the back of unit with Anderson connector connected.
Disconnect Solar Panel from Unit:
Cover the solar panel with an opaque sheet or flip the solar panel with the solar cell facing a flat
ground to minimize the output voltage to zero volts.
Verify the Solar charge indicator is off.
Disconnect the solar cable connector from the solar input port of the unit.
4. CONFIGURATION
Please read the following table to fully understand unit settings and desire your own desirable
settings. Unit default setting is “Full Automatic” (In1, Ch1, Al1).
Understanding of Unit Setting
Inverter
Setting
In0
Inverter is disabled, unit will not provide backup function when utility power is not
available
In1
Inverter is set to standby mode. Unit will provide backup function when utility
power is not available
In2
Inverter is forced to turn on even when AC utility power is available. The inverter
will only switch back to utility mode when internal battery is getting low. With this
setting, the 2A internal AC charger is set to Ch0 by default. (use this mode only if
sufficient solar panel is equipped)
Alarm
Setting
AL0
Audio alarm sound is disabled. Alarm will not sound when warning and fault occur.
AL1
Audio alarm sound is enabled. Alarm sounds when warning or fault occurs.
Unit Function Setting
Setting
Mode of
Operation
Unit Function
In1
AL1
Full
Automatic
(Factory
default)
AC output is provided by AC utility when utility is available.
Internal battery is automatically charged by the 2A charger. AC
output will automatically switch to inverter mode power by the
internal battery when utility is not available. Audio alarm is
enabled and will sound when any warning or fault occurs.
In1
AL0
Full
Automatic
Silent
Same as “Full Automatic” mode but with alarm disabled. Audio
alarm will not sound when any warning or fault occurs. The unit
fault protection features remain active and will shut down without
audio warning when fault occurs.