User's Manual
Appendix A Status Codes
NI-DAQ FRM for PC Compatibles A-20
©
 National Instruments Corporation
–10783 calConstPolarityConflictError Calibration constants in the load area 
have a different polarity from the 
current configuration. Therefore, if you 
receive this error, you should load 
constants from factory. If you receive 
status +10783, be aware that NI-DAQ 
has automatically loaded constants from 
the factory.
–10800 timeOutError The operation could not complete 
within the time limit.
–10801 calibrationError An error occurred during the calibration 
process.
–10802 dataNotAvailError The requested amount of data has not 
yet been acquired.
–10803 transferStoppedError The transfer has been stopped to prevent 
regeneration of output data.
–10804 earlyStopError The transfer stopped prior to reaching 
the end of the transfer buffer.
–10805 overRunError The clock rate is faster than the 
hardware can support. An attempt to 
input or output a new data point was 
made before the hardware could finish 
processing the previous data point. This 
condition also can occur when glitches 
are present on an external clock signal.
–10806 noTrigFoundError No trigger value was found in the input 
transfer buffer.
–10807 earlyTrigError The trigger occurred before sufficient 
pretrigger data was acquired.
–10808 LPTCommunicationError An error occurred in the parallel port 
communication with the DAQ device.
Table A-1. 
Status Code Summary (Continued)
Status Code Status Name Description