User's Manual
Chapter 2 Function Reference — Select_Signal
©
 National Instruments Corporation 2-379 NI-DAQ FRM for PC Compatibles
Use ND_OUT_START_TRIGGER to initiate a waveform generation sequence. You can use an 
external signal or the signal used as the 
ND_IN_START_TRIGGER, or NI-DAQ can generate 
it. Setting source to 
ND_IN_START_TRIGGER is useful for synchronizing waveform 
generation with data acquisition.
By setting source to 
ND_IO_CONNECTOR, you can trigger using a signal on the I/O connector 
pin. For finding out which pin on the I/O connector is the external trigger input, refer to your 
DAQArb 5411 User Manual.
If you do not call this function with signal = 
ND_OUT_START_TRIGGER, NI-DAQ uses the 
default values, source = 
ND_AUTOMATIC and sourceSpec = ND_LOW_TO_HIGH.
signal = 
ND_OUT_UPDATE
Note DAQARB 5411 devices do not have DAQ-STC on board.
Use this signal for update timing. You can use a DAQ-STC timer for timing the updates, or 
you can use an external signal. You also can use output of the general-purpose counter 1 for 
update timing. 
If you do not call this function with signal = 
ND_OUT_UPDATE, NI-DAQ uses the default 
values, source = 
ND_INTERNAL_TIMER and sourceSpec = ND_LOW_TO_HIGH.
signal = 
ND_OUT_EXTERNAL_GATE 
ND_AUTOMATIC ND_LOW_TO_HIGH
ND_IO_CONNECTOR ND_LOW_TO_HIGH
source sourceSpec 
ND_PFI_0 through ND_PFI_9 ND_LOW_TO_HIGH and ND_HIGH_TO_LOW
ND_RTSI_0 through ND_RTSI_6 ND_LOW_TO_HIGH and ND_HIGH_TO_LOW
ND_GPCTR1_OUTPUT
ND_LOW_TO_HIGH and ND_HIGH_TO_LOW
ND_INTERNAL_TIMER ND_LOW_TO_HIGH
source sourceSpec 
ND_PFI_0 through ND_PFI_9 ND_PAUSE_ON_HIGH and ND_PAUSE_ON_LOW
ND_RTSI_0 through ND_RTSI_6 ND_PAUSE_ON_HIGH and ND_PAUSE_ON_LOW
ND_NONE ND_DONT_CARE
source sourceSpec 