Full-scale output current
Minimum.................................... 20.1 mA
Typical ........................................ 20.6 mA
Maximum ................................... 21.0 mA
Output range ..................................... 0 to 20 mA
Compliance voltage .......................... 12 VDC max
Maximum load.................................. 600 Ω
Accuracy
Measurement Conditions
Percent of
Reading
(Gain Error)
Percent of
Range
*
(Offset Error)
Calibrated, typ (25 °C, ±5 °C) 0.11% 0.19%
Calibrated, max (–40 to 70 °C) 0.25% 0.4%
Uncalibrated, typ (25 °C, ±5 °C) 0.35% 1.4%
Uncalibrated, max (–40 to 70 °C) 0.85% 2.5%
*
Range equals 0 to 20.6 mA