- NI 6013/6014 User Manual

Chapter 4 Connecting Signals
NI 6013/6014 User Manual 4-4 ni.com
PFI0/TRIG1 DGND Input
Output
PFI0/Trigger 1As an input, this signal is a Programmable
PFI. PFI signals are explained in the Connecting Timing
Signals section. As an output, this signal is the TRIG1
(AI Start Trigger) signal. In posttriggered DAQ sequences,
a low-to-high transition indicates the initiation of the
acquisition sequence. In pretriggered applications,
a low-to-high transition indicates the initiation of
the pretrigger conversions.
PFI1/TRIG2 DGND Input
Output
PFI1/Trigger 2As an input, this signal is a PFI. As an
output, this signal is the TRIG2 (AI Stop Trigger) signal.
In pretrigger applications, a low-to-high transition indicates
the initiation of the posttrigger conversions. TRIG2 is not
used in posttrigger applications.
PFI2/CONVERT* DGND Input
Output
PFI2/ConvertAs an input, this signal is a PFI. As an
output, this signal is the CONVERT* (AI Convert) signal.
A high-to-low edge on CONVERT* indicates that an A/D
conversion is occurring.
PFI3/GPCTR1_SOURCE DGND Input
Output
PFI3/Counter 1 SourceAs an input, this signal is a PFI.
As an output, this signal is the GPCTR1_SOURCE signal.
This signal reflects the actual source connected to the
general-purpose counter 1.
PFI4/GPCTR1_GATE DGND Input
Output
PFI4/Counter 1 GateAs an input, this signal is a PFI.
As an output, this signal is the GPCTR1_GATE signal.
This signal reflects the actual gate signal connected to the
general-purpose counter 1.
GPCTR1_OUT DGND Output Counter 1 OutputThis output is from the general-purpose
counter 1 output.
PFI5/UPDATE* DGND Input
Output
PFI5/UpdateAs an input, this signal is a PFI. As an
output, this signal is the UPDATE* (AO Update) signal.
A high-to-low edge on UPDATE* indicates that the AO
primary group is being updated for the NI 6014.
PFI6/WFTRIG DGND Input
Output
PFI6/Waveform TriggerAs an input, this signal is a PFI.
As an output, this signal is the WFTRIG (AO Start Trigger)
signal. In timed AO sequences, a low-to-high transition
indicates the initiation of the waveform generation.
PFI7/STARTSCAN DGND Input
Output
PFI7/Start of ScanAs an input, this signal is a PFI. As an
output, this signal is the STARTSCAN (AI Scan Start)
signal. This pin pulses once at the start of each AI scan in
the interval scan. A low-to-high transition indicates the start
of the scan.
Table 4-2. Signal Descriptions for I/O Connector Pins (Continued)
Signal Name Reference Direction Description