Intelligent Real-Time Controllers Operating Instructions and Specifications

© National Instruments Corporation 35 cFP-2200/2210/2220
Environmental
The cFP-22xx is intended for indoor use only, but it may be used outdoors
if mounted in a suitably rated enclosure.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2)........... 40 to 70 °C
Note To meet this operating temperature range, follow the guidelines in the installation
instructions for your Compact FieldPoint system.
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2)........... –55 to 85 °C
Ingress protection................................... IP 20
Operating humidity
(IEC 60068-2-56)................................... 10 to 90% RH, noncondensing
Storage humidity
(IEC 60068-2-56)................................... 5 to 95% RH, noncondensing
Maximum altitude .................................. 2,000 m
Pollution Degree (IEC 60664) ............... 2
Shock and Vibration
To meet these specifications, you must panel mount the Compact
FieldPoint system and affix ferrules to the ends of the power terminal wires.
Operating shock
(IEC 60068-2-27)................................... 30 g, 11 ms half sine;
50 g, 3 ms half sine;
18 shocks at 6 orientations
Operating vibration,
random (IEC 60068-2-64)...................... 5 g
rms
, 10 to 500 Hz
Operating vibration,
sinusoidal (IEC 60068-2-6).................... 5 g, 10 to 500 Hz
Special Conditions for Marine Applications
Some products are Lloyd’s Register (LR) Type Approved for marine
applications. To verify Lloyd’s Register certification, visit
ni.com/
certification
and search for the LR certificate, or look for the Lloyd’s
Register mark on the product.