Installation Guide

30
W415-0794 / B / 11.03.10
Outlet pressure can be adjusted if not
measuring 3.5” W.C. (NG) or 10.0” W.C. (LP).
A. Pressure can be checked by
removing cap (A) using a 3/16 Allen
key and replacing it with a 1/8 NPT
barb tting.
B. Place pressure gauge tube over the
tting.
C. Pressure can be adjusted by
removing cap (B) using a at
screwdriver, and adjusting the nylon
plug with the same screw driver.
Turning the plug in (clockwise) will
increase the pressure.
9.0 ADJUSTMENTS
9.1 GAS PRESSURE ADJUSTMENT
AIR SHUTTER OPENINGS
LP 5/16” DIA (x2)
NG 3/16” DIA (x1)
It is important to periodically perform a visual check of the burner ame. Compare
them to the illustration provided.
9.2 VENTURI ADJUSTMENT
This model has an air shutter that has been factory set open according to the chart below:
Closing the air shutter will cause a more yellow ame, but can lead to carboning.
Opening the air shutter will cause a more blue ame, but can cause ame lifting
from the burner ports. The ame may not appear yellow immediately; allow 15
to 30 minutes for the nal ame color to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
NOTE: It is important that the venturi sits down tight on the ori ce.
49.3
VENTURI
BURNER
AIR
SHUTTER
OPENING
9.3 FLAME CHARACTERISTICS