Installation Instructions

WARNING!
The cylinder valve(s) must be readily accessible for hand operaon. A door on the enclosure to gain access
to the cylinder valves is acceptable, provided it is non-locking and can be opened without the use of tools.
The enclosure for the LP-gas cylinder must isolate the cylinder from the burner compartment to provide
shielding from radiaon, a ame barrier, and protecon from foreign material, such as hot drippings. The
enclosure cannot be located directly below the grill.
There must be a minimum clearance of 2 in (51 mm) between the oor of the LP-gas cylinder enclosure
and the ground.
The enclosure must be designed so that the LP-gas cylinder can be connected, disconnected and the
connecons inspected and tested outside the cylinder enclosure. Any connecons that can be disturbed
when installing the cylinder in the enclosure must be accessible for tesng inside the enclosure.
BUILT IN NATURAL GAS HOOK-UP: The piping up to the gas grill is the responsibility of the installer and piping
should be located as shown in the built-in instrucons. A exible metal connector is included to simplify the
installaon of the unit. Connect this connector to the are ng on the end of the manifold. Connect the
other end of the connector to the gas piping. Ensure that the connector does not pass through a wall, oor,
ceiling or paron, and is protected from damage. Do not use hose to connect the unit. It must be connected
with rigid pipe, copper tube or an approved exible metal connector which complies with Z21.4 /CSA 6.10.
The installaon must comply with CAN B149.1 Natural Gas and Propane Installaon Code in Canada, or to the
Naonal Fuel Gas Code, ANSI Z223.1 in the United States. The gas supply pipe must be suciently sized to
supply the BTU/h specied on the rang plate, based on the length of the piping run. If installing a side burner,
a separate line must be branched o to the side burner unit and enter the side burner opening at the specied
locaon.
WARNING!

WARNING!
DANGER!


CYLINDER SIZE OPENING A AREA OPENING B AREA
20 lb (9.1kg)
20in
2
(130cm
2
) 10in
2
(65cm
2
)
30 lb (13.6kg)
30in
2
(195cm
2
) 15in
2
(100cm
2
)




OPENING
A
OPENING
B


PARTITION TO ISOLATE

NON LOCKING DOOR



