User Manual
Modbus user manual | NANO-NL | November 1, 2022 | version 1.0 page 6
Register
Name Description length
40088 Event count: fault external hold open Nr. Of events occurred since reboot 1
40089 Event count: fault external hold shorted Nr. Of events occurred since reboot 1
40090 Event count: fault external hold midrange Nr. Of events occurred since reboot 1
40091 Event count: fault external release open Nr. Of events occurred since reboot 1
40092 Event count: fault external release shorted Nr. Of events occurred since reboot 1
40093 Event count: fault external release midrange Nr. Of events occurred since reboot 1
40094 Event count: fault power disconnected Nr. Of events occurred since reboot 1
40095 Event count: external release Nr. Of events occurred since reboot 1
40096 Event count: external hold Nr. Of events occurred since reboot 1
40097 Event count: firezone 1 fire Nr. Of events occurred since reboot 1
40098 Event count: firezone 2 fire Nr. Of events occurred since reboot 1
40100 Event count: charged cap Nr. Of events occurred since reboot 1
40103 Event count: vehicle mode 1 = Active, 0 = Not active 1
40104 Event count: backup power mode 1 = Active, 0 = Not active 1
40105 Event count: usb power connected 1 = Active, 0 = Not active 1
40130 Led state: ext release fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40131 Led state: power 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40132 Led state: manual mode 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40133 Led state: zone 1 alarm 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40134 Led state: zone2 alarm 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40135 Led state: zone1 fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40136 Led state: zone 2 fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40137 Led state: general fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40138 Led state: fire1 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40139 Led state: auto mode 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40140 Led state: released 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40141 Led state: delay 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40142 Led state: hold 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40143 Led state: exting fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40144 Led state: sounder fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40145 Led state: backup power 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40146 Led state: ext hold fault 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40147 Led state: fire2 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40148 Led state: fire3 0 = off, 1 = on, 2 = blink, 3 = blink fast 1
40150 VFC state: Fire 1 = Active, 0 = Not active 1
40151 VFC state: Fault 1 = Active, 0 = Not active 1
40152 VFC state: Fan 1 = Active, 0 = Not active 1
40153 VFC state: Extinguish 1 = Active, 0 = Not active 1
40160 Button state: Reset
0 = not pushed, 1 = pushed, 2 = pushed long,
3 = pushed longer
1
40161 Button state: Hold
0 = not pushed, 1 = pushed, 2 = pushed long,
3 = pushed longer
1
40162 Button state: Mode
0 = not pushed, 1 = pushed, 2 = pushed long,
3 = pushed longer
1
40163 Button state: Mute
0 = not pushed, 1 = pushed, 2 = pushed long,
3 = pushed longer
1