User Manual

www.N2KB.nl page 13
19 W
IRING & CABLE SPECIFICATIONS:
There is NO need for shielded cable
Use a pair twisted cable, this strength the protection against electrical or magnetic field.
Minimal solid copper core diameter, extinguisher line cable <50 meters length 1,0 mm² (AWG 18)
Minimal solid copper core diameter, extinguisher line cable >50 meters length 1,5 mm² (AWG 16)
Minimal solid copper core diameter, fire detection cables 0,5mm² (AWG 20)
Maximum solid copper core diameter other cables 1,0mm² (AWG 18)
Maximum conductor loop resistance extinguisher line cable is 24 Ω/km.
Maximum cable length of the fire zone cables is 50 meters
Maximum cable length of the cable from NANO to ETB is 30 meters
The total cable length of all extinguishers together is max 100 meters in total
20 T
ECHNICAL SPECIFICATION
Environment
Ambient Temperature Range -25 to +55 degrees Celsius
Dust and water rating IP65
Compass safe distance minimum 50 mm
Power related specification
Input voltage main and emergency battery 12/24 VDC +/-30%
Maximum power usage 1 Watt quiescent 5 Watt in alarm
Maximum contact rate relays 30 VDC/1A
Voltage fire zone 15 Vdc
Limited alarm current fire detectors 60 mA
Aerosol extinguisher output specification
Maximum Stat-X extinguisher count 5 connected on ETB max 100 meter cable
Maximum Stat-X extinguisher count 7 connected without ETB max 100 meter cable
Extinguisher release current 1,3A
Extinguisher release pulse length 50 ms
Solenoid extinguisher output specification
End of line component 2 x back - EMF diodes 1N4004 or equal
Maximum number solenoids 1
Maximum coil resistance 25 to 200 ohms
Maximum current 1 A
Voltage 24Vdc
Extinguisher release pulse length 8 seconds
Detection zone, hold and extinguishing release inputs
Normal state > 8 kΩ < 12 kΩ
Alarm load < 100 Ω >1.2 kΩ
Zone fault thresholds < 100 Ω I > 1.2 kΩ < 8 kΩ I > 12 kΩ
Alarm resistant 470 Ω
End of line resistant 10 kΩ