Technical data
08
KICKSPACE
®
500, 600, 600-12V & 800
9.0 Technical Data (continued...)
Model Fan Speed
Heat Output (watts)
Temperature Difference (°C)
Heat Output (Btu/h)
Temperature Difference (°F)
733 815 896 976 1056 1135
923 1045 1166 1289 1412 1535
880 1053 1225 1393 1560 1730
1275 1453 1630 1803 1975 2150
880 1053 1225 1393 1560 1730
1275 1453 1630 1803 1975 2150
1396 1552 1707 1860 2012 2162
1738 1964 2192 2420 2649 2879
Normal
Boost
Normal
Boost
Normal
Boost
Normal
Boost
2501 2781 3058 3332 3603 3873
3152 3565 3981 4398 4817 5238
3002 3594 4179 4754 5322 5904
4350 4959 5561 6154 6738 7336
3002 3594 4179 4754 5322 5904
4350 4959 5561 6154 6738 7336
4763 5295 5824 6346 6865 7377
5930 6701 7479 8257 9038 9823
40° 45° 50° 55° 60° 65° 72° 81° 90° 99° 108° 117°
Noise Levels
Heat outputs tested in accordance with
BS 4856 Part 1.
Flow Rate: 340 ltr/h (75 gal/h).
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply output by 1.03.
227 ltr/h (50 gal/h) multiply output by 0.96.
113 ltr/h (25 gal/h) multiply output by 0.85.
Noise levels tested in accordance with EN 23741.
*Includes transformer.
Model
Sound Pressures at 2.5m (dBA)
500 25.7 38.1
600 26.4 37.2
600-12V 26.4 32.7
800 28.5 49.8
Normal Boost
Weight, Water Content and Motor Power
Model
Motor
Power (W)
Water
Content (l)
Unit Weight
(kg)
500 25 0.15 5.5
600 40 0.30 5.9
600-12V 40 0.30 6.9
800 40 0.18 5.5
Heating Performance Data
Approximate Hydraulic Resistance through Fan Convectors
Litres/h
500
788
488
231
82
600
1046
625
326
95
600-12V
1046
625
326
95
800
911
544
258
82
500
7.7
4.8
2.3
0.8
600
10.3
6.1
3.2
0.9
600-12V
10.3
6.1
3.2
0.9
800
8.9
5.3
2.5
0.8
455
340
227
113
mm wg
kPa
500
600
600-12V
800
*
Fan Selector
Switch
Summer/Winter
Switch
LOW LIMIT
THERMOSTAT
MOTOR
Chassis
Earth
br
bl
L
N
g/y
bl
y
r
bl bl
Fig. 10 KICKSPACE
®
500, 600 & 800 wiring diagram