9.0 Electrical Connection
l The electrical installation must comply with local or national
wiring regulations.
l This unit is supplied fitted with a 2 metre 0.75mm
2
cord.
l For KICKSPACE
®
500, 600 and 800, a fused (3A) electrical spur
with a switch having 3mm separation on all poles must be
provided in an easily accessible position adjacent to the unit
(see Fig. 8).
l For the KICKSPACE
®
600-12V, a fused electrical spur having
3mm separation on all poles must be provided in an easily
accessible position adjacent to the transformer. Both the fused
spur and the transformer must not be positioned in a bathroom
or other similar high humidity installation (see Fig. 9).
l Room Thermostat - If a remote room thermostat is required,
wire it into the fused spur at this stage (not KICKSPACE
®
600
12V).
l Remote Control Switch - A remote control switch is available as
an accessory, and if required should be wired at this stage.
l If the supply cord to KICKSPACE
®
models 500, 600 or 800 is
damaged, it must be replaced by the manufacturer, its
service agent or similar qualified persons in order to avoid a
hazard.
l If the supply or outlet cord to KICKSPACE
®
600-12V
transformer is damaged, it must be replaced by the
manufacturer, its service agent or similar qualified persons in
order to avoid a hazard.
l For the KICKSPACE
®
600-12V, a connector block is supplied to
connect the low voltage supply from the transformer to the
supply cord fitted to the unit.
WARNING: KICKSPACE
®
500, 600 and 800 models must be earthed.
Do not energise the electrical supply until the remaining stages of the installation have been completed.
Fan Selector
Switch
Summer/Winter
Switch
LOW LIMIT
THERMOSTAT
MOTOR
Chassis
Earth
br
bl
L
N
g/y
bl
y
r
bl bl
Fig. 8 KICKSPACE
®
500, 600 & 800 wiring diagram
8.0
9.0
KICKSPACE 500, 600, 600-12V & 800 INSTALLATION & MAINTENANCE MANUAL
01.01.2013 ISSUE 6
26690 Kickspace Manual for web_Layout 1 24/09/2013 10:08 Page 8