iVECTOR Heater/Cooler
3.0 Heating System Design (continued...)
1
/
2
"
4"
4"
6"
6"
Note: Pressure independent balancing and control valve kits
are available for this product as an accessory. The valve
kits can simplify system design by eliminating the possible
need for larger balancing valves elsewhere in the system, and
will maintain the flow in the unit to the required levels. See
accessories section for more details.
NB: Pipes should be sized using flow rate and pressure losses.
4.0 Unit Selection/Sizing
Heating output performance data is given in the technical data
section of this manual (see page 15). Outputs are shown for the
three fan speeds, however, it is important to size the unit to
match the calculated heat loss requirements of the room with
the unit operating on the normal fan speed. The higher fan
speeds are used in Comfort mode when the room temperature
is significantly lower than the preset temperature.
Note: It is also possible to electronically remove the highest fan
speed from the functionality of this unit via the control system
(see page 20). This may be advantageous on low temperature
systems to prevent cool air being blown into the room on the
highest setting.
When establishing the temperature difference,
i.e. entering
water to room temperature difference, allowance should be
made for the temperature drop in the system. It is the water
temperature at the unit that dictates the output.
5.0 Location
This unit may be fitted to any convenient wall at a height from
the floor level that suits the application, providing an unimpeded
flow of air into the area to be heated/cooled.
For cooling applications, the need for disposal of condensate
may influence the position of the unit.
Mount on a
flat wall with
sufficient side
clearance
NO mounting
on uneven wall
surfaces
No microbore pipework