Instructions / Assembly
16
iVECTOR Heater/Cooler
The iVECTOR should be sized based on “normal” outputs.
All iVECTOR models require an electrical supply of 120V 60Hz.
Electrical Data
Air Flow Rates
Normal 53 80 106 132 159
Heating Medium 87 130 174 217 261
Boost 145 218 290 363 436
Normal 38 58 77 96 115
Cooling Medium 65 97 129 162 194
Boost 119 178 237 297 356
Air Flow (cfm)
Condition
iV60x080 iV60x100 iV60x120 iV60x140 iV60x160
Fan
Speed
11.0 Technical Data (continued...)
Weight, Water Content and Motor Power
Model
Motor
Power
(w)
2 Pipe
Water
Content
(gal)
4 Pipe
Water
Content
(gal)
2 Pipe
Unpacked
Weight
(lbs)
4 Pipe
Unpacked
Weight
(lbs)
Dimensions
Model
Nominal Height
(ins)
Depth
(ins)
Length
(ins)
iV60x080 23
5
/8 631
1
/2
iV60x100 23
5
/8 639
3
/8
iV60x120 23
5
/8 647
1
/4
iV60x140 23
5
/8 655
1
/8
iV60x160 23
5
/8 663
iV60x080 32 0.174 0.087 50 115
iV60x100 35 0.243 0.1215 61 140
iV60x120 44 0.314 0.6 72 164
iV60x140 53 0.383 0.73 83 189
iV60x160 65 0.454 0.227 94 215
Note: 2 pipe water content = 2 pipe heating/cooling or 4 pipe cooling and 4 pipe
water content = 4 pipe heating.
Model
iV60x080 24.8 37.7 47.9
iV60x100 27 35.8 47.9
iV60x120 24 40.5 51.7
iV60x140 24.9 35.5 54.8
iV60x160 27 35 56.3
Sound Levels
Sound levels tested in accordance with ISO 3741.
Sound Pressure (dBA) (at 2.5m)
Normal Medium Boost
Pressure Drop
100 12 18 23 26 30
150 26 36 47 52 60
220 44 60 78 85 98
330 66 89 115 124 143
500 92 124 157 170 194
750 123 163 205 221 253
Pressure Drop (ins wg)
2 Pipe Heating/Cooling & 4 Pipe Cooling
100 24 36 46 52 60
150 52 72 94 104 120
220 88 120 156 170 196
330 132 178 230 248 286
500 184 248 314 340 388
4 Pipe Heating
Flow
(l/h)
iV60x080 iV60x100 iV60x120 iV60x140 iV60x160
25278 iVector Installation Guide US 02/01/2013 09:25 Page 17