24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 2 Installation, Operating, Maintenance and After Sales Manual. iVECTOR Heater/Cooler Models: iV080, iV100, iV120, iV140, iV160 heatingthroughinnovation. 01.10.2011 ISSUE 1 Product Serial Number: Please leave this manual with the end user.
4197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 3 Contents 1.0 Introduction 03 2.0 Warnings & Safety Measures 03 3.0 Heating System Design 03 4.0 Unit Selection/Sizing 04 5.0 Location 04 6.0 Preparation 05 7.0 Fixing 06 8.0 Water Connection 07 9.0 Electrical Connection 08 10.0 Commissioning Procedure 11 11.0 Technical Data 12 12.0 Control System Set-up and Operating Instruction 13 12.1 Unit Operation 13 12.2 Operating Modes 15 12.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 4 iVECTOR Heater/Cooler 03 A range of accessories are available for this product including control valves and condensate pumps for cooling installations. The control system provides thermostatic room temperature and fan speed control, and allows operation on a stand-alone basis, or by integration into building management systems. This manual should be read carefully prior to installation and retained for future reference. 2.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 5 04 iVECTOR Heater/Cooler 3.0 Heating System Design (continued...) Model Minimum Pipe Size (mm) (2 pipe units) iV080 15 * iV100 15 ** iV120 22 iV140 22 iV160 22 * 8m max recommended pipe run. Increase pipe diameter if longer run is needed. ** 4m max recommended pipe run. Increase pipe diameter if longer run is needed. Note: A pressure independent balancing and control valve is available for this product as an accessory.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 6 iVECTOR Heater/Cooler 05 6.0 Preparation Before proceeding with the installation, remove the carton lid, unpack the contents carefully and check against the checklist below: 1. Heater Cooler unit (chassis) 2. Outer Casing 3. Warranty Card 1 3.0 4. Instruction Manual 5. Fixing kit Check contents for concealed shipping damage. 2 rran Wa ty 3 4.0 Tools required: 4 nu a l 5.0 Ma 6.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 7 06 iVECTOR Heater/Cooler 7.0 Fixing 1. 2. B 236 236 3. 4. 5. 6. NOTE: Do not replace outer cover until connection to system and connection to electrical supply has been completed.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 8 iVECTOR Heater/Cooler 07 8.0 Water Connection Connect the unit to the flow and return pipes. Pipe-work can be routed from the floor or through the wall at the back of the unit. (See options below). Connections are G3/4". needed and can be removed by unscrewing the two bracket fixing screws. Removal of this component will aid pipe-work fitting when the pipes are routed up from the floor.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 9 08 iVECTOR Heater/Cooler 8.0 Water Connection (continued...) How to bleed/vent Condensate drain connection Spiggot size 15mm O/D Connecting tube >15mm I/D Ensure all water fittings are secure before filling the heating system. A drain tray is fitted for condensate collection within the unit. This should be connected to a 15mm drain pipe.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 10 iVECTOR Heater/Cooler 9.0 Electrical Connection 09 (continued...) 1. Remove x 2 screws to access control panel 2. Remove control panel cover Refer to wiring diagrams on pages 10 & 11. 3. Routing cable After making the electrical connections replace the side cover to the control box. BMS Connection 8.0 Control Valve Connection Live Neutral 9.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 11 10 iVECTOR Heater/Cooler 9.0 Electrical Connection (continued...
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 12 iVECTOR Heater/Cooler 9.0 Electrical Connection 11 (continued...) 2-pipe 1 valve + BMS 24V AC BUILDING MANAGEMENT SYSTEM Supply 230V 50Hz 24V 50Hz 24V DC COM FAST SLOW HEAT COOL + - CONTROL BOARD POWER BOARD R W Y M+ T+ Supply 230V 50Hz L N TM- BR Hi R WATER SENSOR 2-PIPE Med W Lo Y AIR SENSOR FAN BL TRANSFORMER 10.0 9.0 10.0 Commissioning Procedure 1 2 1. l Fill and vent the system.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 13 12 iVECTOR Heater/Cooler 11.0 Technical Data Dimensions Weight, Water Content and Motor Power Model Nominal Height (mm) Depth (mm) Length (mm) Model Motor Power (w) Water Content (l) Unpacked Weight (kg) iV60x080 600 153 800 iV60x080 32 0.66 22.8 iV60x100 600 153 1000 iV60x100 35 0.92 27.7 iV60x120 600 153 1200 iV60x120 45 1.19 32.5 iV60x140 600 153 1400 iV60x140 53 1.45 37.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 14 iVECTOR Heater/Cooler 13 12.0 Control System Set-up and Operating Instruction General Description Additional functions are available if necessary from the Full operating mode menu. The electronic control system on this unit provides a wide range of options that can be selected according to system complexity and operating requirements.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 15 14 iVECTOR Heater/Cooler 12.1 Unit Operation (continued...) Easy Mode Display 1. Heating indicator 2. Cooling indicator 3. Temperature symbol – when this is displayed the current room temperature is displayed 4. Fan speed symbol (fan blades will rotate when active) 5. Comfort setting 6. Power (on/off) 7. Clock setting 8. Room temperature 9. Time 10.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 16 iVECTOR Heater/Cooler 15 12.2 Operating Modes Use ( ) and ( ) keys to choose from the following parameters. A function is selected when the icon is surrounded by . Description Control Operation Setup Control Operation Setup The unit must be programed for operation in heating only, cooling only or heating and cooling. Scroll to the Fixed Fan mode , and then press on the ( ) key.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 17 16 iVECTOR Heater/Cooler 12.3 Installer’s Set-up Parameters The various parameters that can be defined by the installer are shown in the table below. To access the installation parameters menu, scroll to AUTO, then press (OK) for 10s. Use ( ) and ( adjusted. Parameter Name dEG 00:00 ) keys to highlight the parameter to be Press (OK) to toggle the parameter setting or edit the value.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 18 iVECTOR Heater/Cooler 17 12.5 Program Mode P Program Menu A quantity of 9 built-in (P1 - P9) and 4 user defined (U1 - U9) timed program options are available to choose from. Each day is divided into 24 one hour periods operating in either Comfort setting (21°C default) or Night set-back setting (19°C default). Use the (+) and (-) keys to scroll through the program options. 1.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 19 18 iVECTOR Heater/Cooler 13.0 Troubleshooting Please follow the troubleshooting guide below before calling for assistance. It is important to make sure that an apparent problem with this unit is not the result of system controls being Problem Heating Mode/ Cooling Mode No Fan incorrectly set, that there is no electrical supply to the unit or that the unit is incorrectly set.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:49 Page 20 iVECTOR Heater/Cooler 19 14.0 Maintenance Disconnect from the power supply before carrying out maintenance work. Maintenance should be restricted to occasional removal of dust and lint around the unit. The outer surface may be wiped over with warm water and mild detergent taking care to avoid water entering the grille areas.
24197 iVector Installation Guide V2_Layout 1 28/11/2011 14:48 Page 1 MYSON Eastern Avenue, Team Valley, Gateshead, Tyne & Wear NE11 0PG, UK T: 0845 402 3434, F: 0191 491 7568, sales@myson.co.uk, www.myson.co.uk heatingthroughinnovation. After Sales Service: Spare parts and technical help on all Convector products are available from MYSON Service. 01.10.2011 ISSUE 1 MYSON Service, Somerden Road, Hull, East Yorkshire HU9 5PE T: 01482 713927, F: 01482 789056, service.convectors@myson.co.