Technical data
09
HI-LINE Super RC
08
HI-LINE Super RC
11.0 Operating Instructions
Description
This HI-LINE Super unit is fitted with a control system that
provides either automatic or manual control of the unit. In
automatic mode the desired temperature set point is selected
and the unit will adjust the fan speed according to the difference
between the actual room temperature and the set point. When
the room temperature reaches the set point the fan will switch off
and thereafter will continue to cycle on and off to maintain the
room temperature. The temperature set point range is 15 - 35°C.
In manual mode any of the three fan speeds can be selected by
overriding the automatic temperature control. This means that
air circulation can be provided in summer for example, or that
heating performance can be controlled manually.
The unit can be controlled using the infra red remote control
handset supplied with the unit (see fig. 5) and also using the
control panel on the unit (see fig. 6). If necessary, however, the
control panel can be locked electronically to prevent tampering
once the controls have been set (see below).
The remote control hand set takes 2 AAA batteries (not supplied).
10.0 Technical Data
Model Fan Speed
Heat Output (watts)
Temperature Difference (°C)
Heat Output (Btu/h)
Temperature Difference (°F)
3906 4432 4962 5496 6033 6573
5526 6281 7045 7815 8591 9373
3417 3843 4270 4697 5123 5550
4800 5500 6200 6900 7600 8400
Normal
Boost
Normal
Boost
29-20
25-18
13327 15122 16930 18752 20585 22427
18855 21431 24038 26665 29312 31981
11659 13112 14569 16026 17480 18937
16378 18766 21154 23543 25931 28661
40° 45° 50° 55° 60° 65° 72° 81° 90° 99° 108° 117°
Air Flow
Heat outputs tested in accordance with
BS 4856 Part 1.
Flow Rate Correction Factors:
455 ltr/h (100 gal/h) multiply by 1.03.
227 ltr/h (50 gal/h) multiply by 0.98.
113 ltr/h (25 gal/h) multiply by 0.85.
Model
Air Flow (m
3
/h) Air Flow (ft
3
/h)
29-20 390 540 13772 19069
25-18 350 500 12360 17657
Min Max Min Max
Weight, Water Content and Motor Power
Model
Motor
Power (W)
Water
Content (l)
Unpacked
Weight (kg)
29-20 80 0.85 21.0
25-18 80 0.63 18.0
Fig. 5 Fig. 6
Controls Display
Power button Switches unit on & off
‘+/-’ button Adjust temperature set point from
15 - 35°C
Scrolls into F1, F2 or F3 manual mode
Heating
Heating will only be provided when the central heating
boiler is on, the pump is running and the system water
temperature is greater than 43°C. Ensure the boiler is on,
and set timer, boiler controls and room thermostats as
necessary.
10.011.0
Heating Performance Data
Approximate Hydraulic Resistance through Fan Convectors
Litres/h
25- 18
2095
1282
620
234
29-20
2551
1530
850
245
25- 18
20.5
12.6
6.1
2.3
29-20
24.6
15.0
8.3
2.4
455
340
227
113
mm wg
kPa