9.0 Commissioning Procedure
G Fill and vent the system.
G Open both valves fully and check for leaks at pipe
connections.
G Refit the outer case and secure using the 2 fixing screws.
G Switch on electrical supply.
G Check the operation of the unit by following the operating
instructions.
G When installation and commissioning are complete, hand over
instruction manual to end-user.
Heat Pump Applications - Low Water Set Point
Adjustment Heating Mode
The low limit water set point is factory set to 43°C but for
systems such as those with heat pumps, a lower water set point
may be required. The set point can be adjusted using the set
point switch located on the control board.
G Isolate electrical supply.
G Remove outer cover.
G Change switch position (see fig. 4).
G Refit outer cover.
G Switch on electrical supply.
Displayed Temperature Calibration
This function enables calibration of the displayed temperature
to the actual room temperature using the following procedure:
G Press the On/Off key and + key simultaneously for 5 seconds.
The display will flash, alternating between ‘ro’ and the
calibration temperature.
G Calibrate the displayed temperature by using the + and –
keys.
G Press the On/Off key to finish.
G This unit is supplied with factory fitted test leads. Remove
these and discard.
G A fused electrical spur with a maximum 3A fuse and a switch,
having 3mm separation on all poles, must be provided in an
easily accessible position adjacent to the unit.
G Electrical cable entry to the unit should be made through the
hole provided at the top left hand side of the unit, using the
cable gland provided.
G Connect live and neutral wires to the power board terminal
connections, and the earth wire to the chassis earth terminal.
8.0 Electrical Connection
WARNING: This appliance must be earthed. The electrical installation must comply with local or national
wiring regulations.
O O
LN
Motor
Power Board
Control Board
Air Sensor
Water Sensor
O O
Brown
Blue
Fig. 4
Switch Switch Down Switch Up
1 Water Stat Set Point 32°C 43°C
2 Heating / Cooling Heating & Cooling Heating
3 Not Used
4 Temperature Display °F °C
8.09.0
Wiring diagram