Installation Guide
Revision 1.1, November 2022 D3510
United Kingdom
zappi
RCD Board Replacement
Installation Guide
myenergi Part Codes
A3552-5-S, A3552-7-S
What’s in the box?
1x RCD Board
SAFETY INFORMATION
Compatibility
The part codes listed above are compatible with
zappis
with serial number
beginning with a ‘2’. These instructions relate only to the part codes above.
Separate instructions required for the installation of an RCD Board in earlier
zappi models.
Installation
Step 1: Isolate the supply to the zappi.
Step 2: Unclip the front fascia and leave to one side.
Step 3: Undo the 8 screws holding the main enclosure cover to the body, and
carefully pull the cover forwards.
Step 4: Unplug the ribbon cable from the front cover and lay the cover on a
flat surface ensuring that the cover can’t be scratched.
WARNING
ELECTRIC SHOCK
Installation of the RCD Board involves opening the zappi enclosure. We,
therefore, recommend that this is carried out by a suitably qualified,
competent person to make sure that the work is carried out safely
The supply to the zappi must be isolated before the cover is removed.
NOTICE
The ribbon can be difficult to pull out.
If installing into an untethered zappi, it will not be possible to remove the cover
completely. Let it hang down whilst protecting it from being scratched.