Problems with Points (continued)
Symptom Diagnosis Remedy
All off-board points are
MISSING.
Short on Aux Power,
terminal 3 or ZONEX
power, terminal 24.
Terminals 3 and 24 share a common circuit
breaker. Check wiring and devices connected
to these terminals for shorts or leakage to
ground.
If only one POPEX
module is connected
to the D9124, POPEX
module may be
incorrectly connected
to the D9124 or Data
Expansion Loop may
be disconnected from
POPEX module.
Check POPEX module for correct connections
to the D9124 and the Data Expansion Loop.