Sample Program
The
D9124 Program Record Training Sheet
(74-06802-000) shows the programming
required to support the D1256 Fire Command Center and power indicating circuit
supervision. The program entries shown on this sheet are those which are loaded into the
D9124 before it’s shipped from the factory.
Further Programming Required
: These entries are necessary, but not sufficient by
themselves to set up the panel. You must complete this program for the D9124 to
function.
Programmer Access Reports
If you send a program to the panel, the panel sends a PROG ACCESS OK report ten
seconds after you exit the handler or when you disconnect the programmer. If you make
three consecutive attempts to send or receive a program with an invalid DataLock code,
the panel sends a PROG ACCESS BAD report. Successfully sending or receiving a
program, or powering down the panel, resets the counter.
Programmable Test Features
See
Testing the System
in this manual for information about how to operate these test
features.
Fire Test
The Fire Test provides a way for one person to carry out a fire test without assistance. It
provides the following features:
Reports to the receiver when you start the test, and when you end it.
Annunciates local sounders without sending reports to the receiver.
Automatically resets smoke detectors. You don't have to reset sensors with
DETECTOR RESET after you test each device.
With a local printer installed, you can print a record of each alarm test response.
Using Fire Test
Fire Test suppresses alarms and troubles:
All alarm and trouble reports to the receiver
are suppressed when fire test is in progress.
Make sure you have DETECTOR RESET enabled when you are using the Fire Test. The
Fire Test is described in
Testing the System
and in the
User’s Guide
provided with the
D1255 and D1255R Command Centers.
Walk Test
The Walk Test is carried out in the same manner as the Fire Test, but it tests points that
turn on and off as part of an intrusion system.
Service Walk Test
The Service Walk Test is carried out in the same manner as the Fire Test, but it tests all
points.