Installation manual

D9124 Operation & Installation Manual
Page 43
© 1996 Radionics
74-06799-000-D 2/96
PERIPHERAL DEVICE CONNECTIONS
Operation Monitor
Pulses When Normal
Flickers When Ringing
Solid When Held In Reset
RED
YELLOW
GREEN
BLACK
32
POWER +
DAT BUS A
DATA BUS B
COMMON
31
30
29
Reset Pin
Disable All Except Battery
Charging And Local Programming
GRN
RESET PIN
LOCKED (CLOSED)
RESET PIN
NORMAL (OPEN)
Figure 21: Reset Pin
Programming
Programming the Panel
The procedure below describes how to connect and disconnect the D5200 Programmer.
Refer to
D5200 Programmer Operation Manual
(74-06176-000) for complete information
on operating the D5200 programmer.
1.
Panel is fully operational during programming:
Except when the programmer is
sending or receiving, the D9124 is functional while the
programmer is connected to it. It will transmit reports as
programmed.
Locking the Reset Pin reduces false alarms and
increases the speed of
programming:
If you have
supervised command centers or
other supervised devices connected
to the Data Bus (terminals 30 and
31), locking the Reset Pin will speed
communication between the panel
and the D5200.
Radionics recommends that you
lock the Reset Pin in the
LOCKED position to prevent
reports from being transmitted
while you are programming. See
Figure 21
.
2. Plug the D5200 Data/Power cord into the programmer connector (J7) on the
D9112LTB.
3. Advance the D5200 display to a
91129112
program record. See
D5200 Programmer
Operation Manual
(74-06176-000).
Troubles after 30 seconds if the Reset Pin is not locked:
If you don’t enter the
91129112
handler within 30 seconds of connecting the programmer, supervised SDI
devices (command centers, printer interface, etc.) connected to the D9124 generate
SDI trouble reports.
Once the panel generates the SDI trouble reports all command centers, both
supervised and unsupervised, stop responding to key strokes. Entering the D9112
handler or disconnecting the programmer returns the command centers to normal
operation.
4. Perform the desired programming function (send or receive program).
5. Disconnect the programmer.
6. Changes to some program parameters require a reset before they become effective.
Unlock the Reset Pin
Reset Recommended:
Radionics recommends that you disable/restart the panel
after changing program parameters with the D5200 programmer. If you locked down
the reset pin in step 1, release it now to reset the panel. If you didn’t lock the rest pin,
momentarily close it now to reset the panel. See
Figure 21.
Remember that the panel’s on-board buzzer sounds for 10 seconds whenever you
reset the panel.