Installation manual

D9124 Operation & Installation Manual
Page 35
© 1996 Radionics
74-06799-000-D 2/96
Model
Number
Quan.
Used
AC Power
ON
Normal
Current
Each Unit
A
Total
AC Power
OFF
Minimum
Current
Each Unit
B
Total
In Alarm
Maximum
Current
Each Unit
C
Total
All D9124
Devices
1 1 460 x 1 = 460 462 x 1 = 462 874 x 1 = 874
D125B 20 x Quan.= 19 x Quan.= 123 x Quan.=
D129 25 x Quan.= 25 x Quan.= 26 x Quan.=
D192C 20 x Quan.= 20 x Quan.= 10 x Quan.=
D1255 104 x Quan.= 106 x Quan.= 206 x Quan.=
D1256 104 x Quan.= 106 x Quan.= 206 x Quan.=
D1257 104 x Quan.= 106 x Quan.= 206 x Quan.=
D8125 48 x Quan.= 47 x Quan.= 48 x Quan.=
D8127 3 x Quan.= 3 x Quan.= 4 x Quan.=
D8130 5 x Quan.= 5 x Quan.= 54 x Quan.=
D9131 24 x Quan.= 22 x Quan.= 36 x Quan.=
D8129 20 x Quan.= 20 x Quan.=
20 x Quan. +
25 x # relays =
Ratings of other 12 Volt devices (bells, horns, strobes, smoke detectors, and heat detectors) in
the system that are not shown above:
x Quan.= x Quan.= x Quan.=
x Quan.= x Quan.= x Quan. =
x Quan.= x Quan.= x Quan.=
x Quan.= x Quan.= x Quan.=
TOTAL A= TOTAL B=
TOTAL C
2
=
1
D9124 current draw includes:
(1) D9112LTB Control/Communicator
(1) D1256 Fire Command Center
(1) D928 Dual Phone Line Switcher
(1) D8125 POPEX Module
(2) D192C Bell Circuit Supervision Modules
Auxiliary Current and Standby Battery Requirements
Calculations for 12 VDC Devices
All currents are in milliamperes (1 ampere = 1000 milliamperes).
Currents shown in milliamperes (1 ampere=1000 milliamperes).
2
If Total C exceeds 1900 mA, a D8132 is required to provide an additional 1400 mA. You may also use
a UL listed external power supply for this purpose.