74-06799-000-D 2/96
Alarm Power Output for Indicating Circuits
24 VDC Output Terminals 7 and 9
Each Alarm power output terminal (7 and 9) on the motherboard provides 24 VDC,
1.8 Amps maximum of alarm power output for bells, sirens, piezo fire sounders, and
electronic horns and strobes. Current calculations in
Table 10
are based on a 3 Amp
maximum.
Total output power for the D9124 must not exceed 4 Amps:
The total output power
for auxiliary power (terminal 5), and the 24 VDC indicating circuits (terminals 7 and 9)
must not exceed four Amps. Exceeding four Amps will overload the D9142 Power
Supply. See the
Auxiliary Current and Standby Battery Requirements
section,
Calculations for 24 VDC Devices
for more information.
Alarm Power Output Responses
Programming in the
Bell Parameters, Point Index Codes, Point Assignments,
and
Relay
Parameters
determine the response of terminals 7 and 9. See the
D9112 Control/
Communicator Program Entry Guide
(74-06145-000) for programming instructions.
Relay A is terminal 6 on the D9112LTB. Terminal 6 on the D9112LTB controls the output
at terminals 7 and 9 on the D9124 motherboard. Energizing Relay A provides power to
terminals 7 and 9 on the motherboard. The D9112 default program sets Relay A for
A# Fire BellA# Fire Bell
. There is no need to reprogram the relay.