Installation manual
D9124 Operation & Installation Manual
Page 33
© 1996 Radionics
74-06799-000-D 2/96
Power Output
Auxiliary Power Outputs
All external connections at the D9124 motherboard are Power Limited.
12V Auxiliary Power from D9112LTB Terminal 1
The D9124 supplies 1.4 Amps at 10.2 to 14 VDC to power auxiliary devices. A self-
resetting circuit breaker protects the circuit against shorts. Devices powered from this
output must operate within a range of 10.2 to 14 VDC.
24 VDC Power from Motherboard Terminal 5
Use terminal 5 to power smoke detectors or other devices that are reset by interrupting
power. Performing a DETECTOR RESET from the command center momentarily
interrupts 24 VDC power to terminal 5 to reset the smoke detectors.
Power Output Depends on Standby Time Requirements
If your standby requirements call for 24 Hours standby time, the D9142 Power Supply
provides up to .136 Amps at terminal 5 on the motherboard with 3 Amps of bell current
available for five minutes of alarm after a 24 hour period of AC power loss. To increase
this output, use larger capacity batteries in an additional enclosure (up to 38Ah, see
Table 10
).
If your application requirements call for 60 hours of standby time, the D9142 provides
.030 Amps of standby current at terminal 5 on the motherboard with 3 Amps of bell
current available for five minutes of alarm after a 60 hour period of AC power loss. To
increase this output, use larger capacity batteries in an additional enclosure (up to 38Ah,
see
Table 10
).
See the
Auxiliary Current and Standby Battery Requirements
section,
Calculations for 24
VDC Devices
for more information about standby time and available power output.
Total output power for the D9124 must not exceed 4 Amps:
The total output power
for auxiliary power (terminal 5), and the 24 VDC indicating circuits (terminals 7 and 9)
must not exceed four Amps. Exceeding four Amps will overload the D9142 Power
Supply. See the
Auxiliary Current and Standby Battery Requirements
section,
Calculations for 24 VDC Devices
for more information.
Verification/Sensor Reset Relay
Relay B is terminal 7 on the D9112 board. Terminal 7 on the D9112LTB controls the
output at terminal 5 on the D9124 motherboard. When Relay B is energized for
DETECTOR RESET or alarm verification, power to terminal 5 of the D9124 is interrupted.
The D9112 default program sets Relay C for
A# Reset SensorsA# Reset Sensors
. Reprogram
A#A#
Reset Sensors Reset Sensors
for Relay B.
See
Area Parameters A# Verify TimeA# Verify Time,
Point Index Codes
Digits 3 and 6, and
Relay
Parameters
A# Reset Sensors A# Reset Sensors
in the
D9112B Program Entry Guide
(74-06145-000) for
instructions on programming verification/reset relays and points.
Pressing DETECTOR RESET activates verification/reset relays for five seconds. The
panel ignores verification/reset points while the relay is activated.