Installation manual
D9124 Operation & Installation Manual
Page 20
© 1996 Radionics
74-06799-000-D 2/96
CIRCUIT 1 C
SILENCE
UP
DOWN
NORMAL
Signaling Circuit
Figure 10: D192 Bell Silence Switch
Indicating Circuit (24 VDC Horns, Strobes, Bells)
Description
The D192C Indicating Circuit Module supervises the wiring from the control/communicator
to remote alarm indicating devices like horns, strobes, and bells. Wiring is supervised for
open, shorted, or grounded circuit faults.
Signaling devices must comply with the following parameters:
• They must be polarized (DC)
• They must match the voltage rating of the alarm power supply (D9142)
• They must not exceed the current rating of the alarm power supply (D9142)
• Combined, they must not exceed 1.8 Amps on motherboard terminals 7 or 9.
Total output power for the D9124 System must not exceed four Amps:
The total
output power for Auxiliary power (terminal 5), and the 24 VDC indicating circuits (terminals
7 and 9) must not exceed four Amps. Exceeding four Amps will overload the D9142
Power Supply. See
Calculations for 24 VDC Devices
to determine total output
requirements.
Operation
During normal operation, the indicating circuit is supervised for incorrectly installed
devices, opens, shorts, and grounds. If any of these conditions are detected, the panel
indicates a trouble condition at the command center. You can program the panel to report
the condition to the central station.
When the panel detects an alarm, the alarm output circuit triggers the D192C to supply
circuit power from the power supply.
To provide supervision, install the 560Ω, 2 Watt EOL resistor (15-03130-005) beyond the
last indicating device. Two resistors are supplied in the literature package.
Silence Switch
The D192C has a toggle switch that is used to disable the fire alarm indicating devices
while you test the panel (see
Figure 10
). When this switch is toggled up in the SILENCE
(OFF) position, the D192C presents a short circuit to Point 7, causing a trouble response.










