Installation manual

D9124 Operation & Installation Manual
Page 12
© 1995 Radionics
74-06799-000-D 2/95
Connecting the Earth Ground
For safety and to help prevent
damage from electrostatic charges
or other transient electrical surges
you must first ground the system
before making any other
connections. Before connecting the
green wire from the 120 VAC
service, crimp a connector to the
end of it. Place objects on this stud
in the following order:
1. Place a star washer on the
stud.
2. Slip the green wire from the
120 VAC service onto the star
washer on the stud.
3. Place the hex nut on the stud
and tighten firmly.
4. Repeat steps 1 through 3 for the two green wires in wiring harness J1 on the upper
battery shelf.
Connecting the 120 VAC Power Input
Radionics recommends that only a licensed electrician make 120 VAC connections to the
D9124 System. The electrician should make all connections conform to NEC 70 and
connect the D9124 system to a suitable ground connection.
Danger: Turn off the circuit breaker before connecting the 120 VAC to the system.
Leaving the circuit breaker on can cause injury or death by electrocution.
To connect the 120 VAC service to the D9124, follow these steps:
1. If the 120 VAC cabling is already installed go to step 5, if not, go to step 2.
2. Make sure the incoming High Voltage (120 VAC) from the D9124 is disconnected.
Important!
Be sure
that the circuit breaker
is OFF.
3. Remove the knockout
cover on the lower left
side of the D9101
enclosure and install
appropriate hardware
for connection to
conduit.
4. Pull the 120 VAC
Power wires through the conduit hardware installed in the knockout, and into the
transformer enclosure.
5. Using appropriate hardware, connect wires to the flying leads from connector J1 as
shown in
Table 1
.
STUD
STAR WASHER
SHEET METAL PANEL
NUT
LUG
LUG
Figure 5: Wire Connections to Ground Stud
Wire From 120
Volt Service
Connect to D9124
System on...
Green Ground Stud Below D1601
White White (on J1)
Black Black (on J1)
Do NOT turn on the Breaker. LEAVE IT OFF!
Table 1: Connect High Voltage to D9124