Installation manual

D9124 Operation & Installation Manual
Page 10
© 1995 Radionics
74-06799-000-D 2/95
Mounting the D9101 Enclosure
When attaching the enclosure to a surface, use mounting hardware capable of supporting
at least 74 pounds of equipment. You may need to mount a plywood sheet to the wall in
order to support the weight of the panel and batteries.
The enclosure door is removable:
To make mounting the D9124 System easier, open
the door and slide it up and off the hinges.
The enclosure door has a lock and can be tampered. It has a smoke gray window, with a
different lock, so you can see the D1256 Fire Command Center display and access the
keypad without having to open the enclosure. The lock to the window uses the same key
as the Radionics manual pull stations.
The enclosure can be flush or surface mounted.
KNOCK OUTS
KNOCK OUTS
KNOCK OUTS
MOUNTING HOLES
MOUNTING HOLES
0 3.06"
19.06"
16.56"
0
28.06"
23.81"
13.43"
11.00"
MOUNTING HOLE AND
KNOCKOUT PATTERN
*22.12"
5.56"
*36.12"
BACK OF
ENCLOSURE
(INSIDE VIEW)
1.93"
1.18"
22.12"
36.12"
37.32"
23.47"
3"
* MEASURMENTS
INCLUDE ENCLOSURE
MATERIAL THICKNESS
Figure 3: Enclosure Dimensions
Flush Mounting
If you are flush mounting the enclosure, cut and frame an opening 22 1/4" x 36 1/4" x 3"
to accept the enclosure base box. See
Figure 3.
Surface Mounting
1. Remove the door from the enclosure.
2. Remove the necessary knockouts for external connections. See
Figure 3
.
3. Mount the enclosure in the desired location. Use all four mounting holes.
4. Run the necessary wiring throughout the premises and pull the wires into the
enclosure. A single knockout is provided at the top right side of the enclosure. If you
punch other holes, be sure not to let them interfere with the component mounting
locations.
Only route AC conduit into the D1601 Transformer’s enclosure.
Clean Up
Strapping tape is used to hold the door closed during shipping. Sometimes the tape
leaves an adhesive residue. Use alcohol to remove the adhesive residue.