User manual

17
MODEL
PM 848S
Netguard
PM 1188S
Netguard
PM 1512S
Netguard
PM 2016S
Netguard
PM 2520S
Netguard
PM 3024S
Netguard
CAPACITY
800 VA /
640 W
1100 VA /
880 W
1500 VA /
1200 W
2000 VA /
1600 W
2500 VA /
2000 W
3000 VA /
2400 W
INPUT
Acceptable Voltage Range 81-145 VAC or 162-290 VAC
Frequency Range 60/50 Hz (auto sensing)
OUTPUT
Voltage Regulation (AC
Mode)
110/120 VAC or 208/220/230/240 VAC
Voltage Regulation (Batt.
Mode)
±3%(before battery alarm)
Frequency Range (Batt.
Mode)
50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 8% max @ 100% linear load, 15% max @ 100% non-linear load (before alarm)
Transfer Time Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode) Pure Sine Wave
EFFICIENCY
AC Mode 97% 97% 97%
Buck & Boost Mode 90% 90% 90%
Battery Mode 83% 85% 87%
BATTERY
Battery Type & Number 12 V/7 Ah x 2 12 V/9 Ah x 2 12 V/7 Ah x4 12 V/9 Ah x4 12 V/7 Ah x6 12 V/9 Ah x6
Charging Voltage 27.4 VDC ± 1% 54.8 VDC ± 1% 82.1 VDC ± 1%
Typical Recharge Time 4 hours recover to 90% capacity
PROTECTION
Full Protection Overload, short, discharge, and overcharge protection
ALARM
Battery Mode Sounding every 10 seconds
Low Battery Sounding every second
Overload Sounding every 0.5 second
Battery Replacement Alarm Sounding every second
Fault Continuously sounding
PHYSICAL
Dimension,
DXWXH
(mm)
350 x 438 x 88 480 x 438 x 88 600 x 438 x 88
Standard
Model
Net Weight
(kg)
14.8 15.8 23 25 32 35
ENVIRONMENT
Operating Humidity 0-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 45dB
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
* Derate capacity to 80% of capacity when the output voltage is adjusted to 208VAC.
**Product specifications are subject to change without further notice.
6. Specifications