User manual

-14-
Model No.
UPS INPUT NFB
VOLTAGE CURRENT
PowerMust 1080 LCD
300 VAC 10A
PowerMust 2016 LCD
300 VAC 20A
PowerMust 3024 LCD
300 VAC 32A
(2) UPS Output Connection
The output of the UPS is German socket-types. Simply plug the
load power cord to the output sockets to complete connection. Use
one cord for every 5A load.
Model No. Output Socket (pcs)
PowerMust 1080 LCD 2 German type
PowerMust 2016 LCD
3 German type
+ Terminal block
PowerMust 3024 LCD
3 German type
+ Terminal block
The wiring configuration is shown as the following procedure:
a) Remove the small cover of the
terminal block
b) Use 2.5mm
2
wires for wiring
configuration
c) Upon completion of the wiring
configuration, please check
whether the wires are securely
affixed
d) Put the small cover back to the
rear panel
Caution!
Do not connect equipment which would overload the UPS
system (e.g. laser printers)
Connection diagram