5. Connection and Operation
5.1 Inspection:
Inspect the packaging carton and its contents for damage. Please
inform the transport agency immediately should you find signs of
damage.
Please keep the packaging in a safe place for future use.
Note: Please ensure that the incoming feeder is isolated and
secured to prevent it from being switched back on again.
5.2 Connection:
(1) UPS Input Connection
If the UPS is connected via the power cord, please use a proper
socket with protection against electric current, and pay attention to
the capacity of the socket: over 4.5 A for 1K, over 9.3 A for 2K,
over 14.5Afor 3K. If the UPS is connected via wires, it is
recommended to select the 2.5mm2 wire, and the “GND” terminal
should be grounded first by using the green/yellow wire. The
wiring is shown as the following.
The UPS System has an input breaker on the cabinet. But we still
advise users to connect external breakers or protective
components to the input. It is recommended to select the NFB
(Non-Fuse Breaker) instead of the traditional combination kit
including breaker and fuse.
When selecting the NFB, the user can refer to below table for
detailed information when installation.
The system may be installed and wired only by qualified
electricians in accordance with applicable safety regulations!
When installing the electrical wiring, please note the nominal
amperage of your incoming feeder.