User manual

Specification
Power Must
MODEL
400 600 800
CAPACITY VA/W 400/240 600/360 800/480
Voltage Range 81-145VAC / 162-290VAC
INPUT
Frequency 50Hz/60Hz
Voltage
110120VAC/220230240VAC
Voltage Regulation +/- 10%(Battery Mode)
Frequency 50Hz / 60Hz
Frequency Regulation
+/-1 Hz(Battery Mode)
OUTPUT
Output Waveform Modified Sine-wave
Battery Type 12V/4.5Ah 12/28W 12V/34W
Back up Time
10 mins100W
18 mins100W
22 mins100W
BATTERY
Recharge Time 8 Hours to 90% after complete discharge
TRANSFER
TIME
Typical 2-6ms typical, 10 ms max
The LCD will always turn on when UPS work,
INDICATOR LCD Display Models
Including in off charging mode and fault mode
Backup Mode Sounding every 10 seconds
Battery Low Sounding every 1 second
Overload Sounding every 0.5 seconds
Battery replace Sounding every 2 seconds
AUDIBLE
ALARM
Fault Continuous sounding
Buck/boost with
>70% SPS load
Sounding every 0.5sec. after 25min.
And fault after 30 mins
PROTECTION Full Protection
Discharge,Overcharge short circuit
and Overload Protection
PHYSICAL
Dimension (DxWxD)
(mm)
330* 100 * 140
WEIGHT
Net Weight 4.4Kg 5.6Kg 6.1Kg
Operating
Environment
0- 40°C, 0-90 % Relative Humidity (non-condensing)
ENVIRONMENT
Noise Level Less than 40dB
INTERFACE
SmartRS-232
(optional)
Windows family,
Sun Solaris, IBM Aix, Compaq True64,
UnixWare, FreeBSD, HP-UX, Linux and MAC
USB(optional) For Windows family & Mac