Datasheet

3.10.12
Intelligent interface modules
MTW 12,4 MTW 12,4
2- 3-wire 4-wire
Ordering data Art.-No. Art.-No.
INPUT spring clamp/screw terminals spring clamp/screw terminals
±50°C 6644330 6644340
– 50…150 °C 6644331 6644341
0…100 °C 6644332 6644342
0…150 °C 6644333 6644343
0…200 °C 6644334 6644344
0…300 °C 6644335 6644345
0…600 °C 6644336 6644346
Technical data
Supply voltage range 18…30 V DC, smoothed
Supply current max. 80 mA
Cable resistance (without PT100) for 3- and 4-wire technology max. 100 Ohm
Output signals at 0…10 V DC max. 25 mA, overload protected
at 4…20 mA max. 500 Ohm
at 0…20 mA max. 500 Ohm
Tolerance ± 1 % from end value
Temperature range 0…+60 °C
Mounting method DIN-rail mounting to EN 50022
Dimensions H x W x D 90 x 12.4 x 65 mm
Description
The Murrelektronik temperature converter module works in conjunction with a temperature sensor PT100 (IEC 751/EN 60751) and converts the output
from the sensor into a standard signal format of (0…10 V, 0…20 mA or 4…20 mA).
The MTW module supplies a constant current to the PT100 resistor across, which develops a variable voltage.
This will be measured, linearized and converted to the output signal at the OUT terminals.
All three signals can be used at the same time.
The 2-wire technology allows short distances between the MTW and the PT100 sensor to be covered, i.e. <5 m. For longer distances, 3-wire technology
compensates for the cable resistance. For three wire technology, remove the bridge between 2 and 3. For the greatest accuracy, 4-wire technology
compensates for both the outgoing and incoming cables which may have differing resistances or lengths.
Notes
To order screw terminal option omit 66 from the part number.
1)
100°C to 010 V DC or 420 mA with 0.1 % precision on Art.-No. 446098 approx.. 446099 on request.
Circuit diagram
Temperature modules
for PT 100 Sensors
Input
ϑ
Output
PT 100
+24 V
I
1
I
2
GND
GND
U
+24 V
I
1
I
2
GND
GND
U
ϑ
U
E3
E1
E2
Input
ϑ
Output
PT 100
ϑ
U,I
E4
E1
E2
E3