Datasheet

Intelligent interface modules
3.10.9
U,I
f
GND
U
I 1
I 2
+ 24V
f1
f2
f3
GND
GND
Ordering data Art.-No. Art.-No.
OUTPUT spring clamp/screw terminals spring clamp/screw terminals
0…1 kHz/10 kHz/100 kHz 6644245
0…10 V DC/0…20 mA/4…20 mA 6644275
Technical data
Supply voltage range 24 V DC ± 20 % 24 V DC ± 20 %
Supply current max. 60 mA max. 80 mA
Input voltage 0…10 V DC 10…30 V
Input current 0…20 mA/4…20 mA 80…25 mA
Input resistance U: approx. 100 k-Ohm/ I: approx. 75 Ohm approx. 1,2 k-Ohm
Output voltage supply voltage – 0,5 V (short circuit protected)
Output signal 0…1 kHz/0…10 kHz/0…100 kHz 0…10 V, 0…20 mA, 4…20 mA
Response time max. 350 ms
Tolerance 0,5 % from end value
Test insulation voltage 1,5 kV AC 2,5 kV AC
Temperature range -25…+50 °C
Mounting method DIN-rail mounting to EN 50022
Dimensions H x W x D 90 x 12,4 x 65 mm
Description
The new interface module in narrow MIRO casing is able to be used The new interface module in narrow MIRO casing is able to be used
universally. An analogue voltage or current, these are applied to three universally. The frequency, that is applied on the three inputs, will be
inputs, and are galvanically isolated, transformed and stay as square wave galvanically isolated, transformed and stay as an analogue signal on all three
voltage (frequency) on all three outputs symmetrical to disposition. outputs symmetrical to disposition.
The output frequencies are through a 4-pole switch separable in
relation to 1:2, 1:4 and 1:8.
Circuit diagram
M..FW 12,4 MF..W 12,4
INPUT 010 V DC INPUT 01 kHz
INPUT 020 mA INPUT 010 kHz
INPUT 420 mA INPUT 0100 kHz
Analogue converter modules
M..FW 12,4 Voltage/Current-
Frequency
MF..W 12,4 Frequency -
Voltage/Current
Inputs and outputs
galvanically isolated
Notes
To order screw terminal option omit 66 from the part number.
f
U,I
GND
IN
f1
f2
f3
+ 24V
U
I1
I2
GND
GND