MB Cap Ultra Add-on-module 3/24 1A/21S - 85462
MB Cap Ultra Add-on-module 3/24 1A/21S - 85462
Calculation of buffering time
The energy of the capacitor results from the sum of the individual energies of the MB Cap Ultra
3/24 7s and the connected MB Cap Ultra add-on modules (extension modules).
Buffering time in sec. =
Lifetime of the
capacitors
The lifetime of the capacitors is
temperature-dependent!
End of lifetime is reached when the
buffering time has fallen to 70% of
the rated buffering time.
10
20
30
40
Temperature in °C
50 60 70
10
20
30
40
50
60
70
0
Year
Technical Data
Storage capacity : 1 kJ
Operating temperature : -20...60°C
Storage temperature : -20...60°C
Relative humidit : 5% - 85% Thawing not permissible
Max. altitude without derating : 1000 m ü. NN
Miscellaneous:
Input:
Output:
Nominal voltage : 24 V DC
Voltage range : 0 V - 26.4 V DC
Nominal current : 3 A DC
Fuse : 3 A T (internal PTC)
Nominal current : 3 A DC
Fuse DC : 3 A T (internal PTC)
Storage capacity in J x η
Output current x output voltage
Example:
25.5 sec. =
1000 J x 0.9
1.5 A x 23.5 V
Connection
Before installation the data of the MB Cap Ultra 3/24 7s have to be compared with the data of the
MB Cap Ultra add-on modules regarding compliance (see type plate). Connect according to the
indications of the terminals. The terminals Cap. + of the MB Cap Ultra 3/24 7s and of the add-on
modules have to be connected. Then connect the terminals Cap. - of the MB Cap Ultra 3/24 7s and
of the add-on modules. Additional add-on modules can be connected from one module to the next
by looping through from Cap. + and Cap. -.
Connection Terminal S
DC-input 'Cap.' +, - max. 1 mm²
DC-output 'Cap.' +, -
pring clamp
max. AWG 17
resp.
6mm
Cap.
Set-up
The unit is switched-on by connecting the DC supply to MB Cap Ultra 3/24 7s.
If the units are used in installations that require overloads for testing (e.g. acc. to
EN60204-1 / VDE0113 Part 1 19.4 Voltage test) the unit has to be separated from the
test set-up before voltage is applied.
(Original text EN60204-1 Components that are not designed for this test voltage have
to be disconnected during the test.)
Check if the connections are correct before first start-up. Establish electrical
connections only when the installation is disconnected from the supply.
When operating the connected power supply > 24 V lifetime will decrease.
D-71570 Oppenweiler
Uin OK
Input
Output
Operation
Uin OK
Ucap. >
MB UltraCap
Add-On Module
D-71570 Oppenweiler
+
+
MB UltraCap
Add-On Module
D-71570 Oppenweiler
+
+
Wiring
We recommend not to add more than 5 add on modules as the charging time will increase with the
extended capacity.
Up to 5
MB Cap Ultra
Add-on Modules
in connection
with an
MB Cap Ultra
article 85460.
Murrelektronik GmbH
Postfach 1
165
D-71567 Oppenweiler
Telefon +49(0)7191/47-0
Falkenstraße 3
D-71570 Oppenweiler
Telefax +49(0)7191/47-130
Info@murrelektronik.com
http://www
.murrelektronik.com
Murrelektronik GmbH Postfach 1165 D-71567 Oppenweiler Telefon +49(0)7191/47-0
Falkenstraße 3 D-71570 Oppenweiler Telefax +49(0)7191/47-130
Info@murrelektronik.com http://www.murrelektronik.com