Lifetime of the
capacitors
The lifetime of the capacitors is
temperature-dependent!
End of lifetime is reached when the
buffering time has fallen to 70% of
the rated buffering time.
10
20
30
40
Temperature in °C
50 60 70
10
20
30
40
50
60
70
0
Connection
Before installation the data of the DC supply have to be compared with the data on the type plate
and checked for compliance. Connection according to the indications of the terminals (see
simplified diagram and configuration)
In case of overload the DC output current is composed of the max. current of the
buffering module and the current from the supplying DC mains. In order to avoid
overloading of the DC output circuit external protection is required! (For values please
refer to “Technical data”)
Simplified diagram
F
-
+
K1
LAST
30V DC/0.5A
K
DC-DC-converter
Operation
D1
J1
LED3
μC
C1
LED1
LED2
UOutput
UInput
UOKin
Ucap. >
Cap.
+
-
+
-
-
Year
LED
Output
Input
Uin OK
Cap.
Connection Terminal S
DC-input
DC-output (load)
Add-on module 'Cap.' +, - max. 1 mm²
(optional)
Signal
(NO)
pring clamp
max. AWG 17
'U ' +, -
'U '+,-,-
'U OK' ‘switching contact
Uin OK’
Input
Output
in
6mm
Operating modes Status LED Output
LED green, lights up:
Presence system voltage at terminal -
U respectively as long as the
LED green, lights up: Potential-free relay contact,
- Presence external supply, normally open (NO),
i.e. U >U max. contact load 30 V DC/ 0.5 A
-
with
only
Input
Input SYSTEM
unit is internally supplied with energy.
Operation
Uin OK
Ucap. > - LED :
Energy in capacitor > 80%
- LED :
Energy in capacitor > 30%
- LED (0.8Hz):
When the capacitors are charged
80% of the energy
- LED (3.2Hz):
Capacitor discharged (unit supplies
itself)
(Values refer to standard
parameterization)
1)
green, lights up
green, goes off
flashes slowly
flashes rapidly
MB Cap Ultra 3/24 1A/21S - 85460
MB Cap Ultra 3/24 1A/21S - 85460
1)
The alarm contact are coupled with the LED display. When LED lights up signal contact is
closed.
Set-up
The unit is switched-on by connecting the DC supply to the terminal 'U '. LED 'Uin OK' lights
up.
Input
If the units are used in installations that require overloads for testing (e.g. acc. to
EN60204-1 / VDE0113 Part 1 19.4 Voltage test) the unit has to be separated from the
test set-up before voltage is applied.
(Original text EN60204-1 Components that are not designed for this test voltage have
to be disconnected during the test.)
Check if the connections are correct before first start-up. Establish electrical
connections only when the installation is disconnected from the supply.
When operating the connected power supply > 24 V lifetime will decrease.
Operation
After the U is switched on the capacitor is charged. The LED 'U OK' lights up. The capacitor
will only be charged if U is approx. 0.5 V - 1.0 V bigger than U in buffer mode. Charging is
indicated by a slowly flashing LED ' U >'. If the capacitor is almost charged the LED ' U >'
will light permanently. By disconnecting the supply respectively by dropping below the minimum
Input in
Input Output
cap. cap.
3
2
Murrelektronik GmbH
Postfach 1
165
D-71567 Oppenweiler
Telefon +49(0)7191/47-0
Falkenstraße 3
D-71570 Oppenweiler
Telefax +49(0)7191/47-130
Info@murrelektronik.com
http://www
.murrelektronik.com
Murrelektronik GmbH Postfach 1165 D-71567 Oppenweiler Telefon +49(0)7191/47-0
Falkenstraße 3 D-71570 Oppenweiler Telefax +49(0)7191/47-130
Info@murrelektronik.com http://www.murrelektronik.com