Specifications
Section 15 00-02-0671
2014-08-27 - 5 -
Installation with a Weld Collar
1.
The weld collar, P/N 15050375, must be welded into the wall of
the pressure vessel according to code standards and good
welding practices.
2.
Follow above instructions for installation directly into the wall of
the pressure vessel.
NOTE: Weld collar 15050375 can be used ONLY with
model LS200.
Installation Using Murphy External Float Chamber
1.
Install the Murphy float chamber 15051098 or
15700799 on the outside wall of the pressure vessel
using 1-inch NPT piping or use the mounting surface
with a bracket. Position the 2-inch NPT threaded
connection at the height where you want the level
switch to operate. The 2-inch NPT threaded
connection must be positioned away from the tank
wall.
2.
A tee and bleed valve are typically installed at the
bottom of the lower 1-inch pipe riser to allow draining
of the float chamber for servicing or replacement.
NOTE: A typical installation with blocking
and bleed valves is shown at right.
3.
Install the LS200 or LS200N/NDVO/NDVOR in the 2-
inch NPT connection of the float chamber. BE SURE
float travel is not restricted and that the float is tight onto the float shaft.
4.
To complete installation and wiring, follow the instructions for mounting directly into
wall of the vessel and for wiring.
CAUTION: Float extensions cannot be used with float chambers.










