Specifications

Section 15 00-02-0671
2014-08-27 - 6 -
Installation and Adjustment for Pneumatic Models
1.
All pneumatic models operate on the vent
principle. The pneumatic signal source must
be clean, dry instrument-quality air or
natural gas. The input pneumatic signal
must be regulated between 30 and 70 psi
(207-483 kPa) [2 -4.83 bar]. If produced gas is
used as the signal source, it should be taken
after gas passes through the final scrubber. A
suitable filter must be positioned before the
LS200NDVO to prevent liquids and/or
particulates from entering the dump valve
operator.
NOTE: Check filter periodically for wear and tear and elements that
hamper the flow of the pneumatic signal.
2. All pressure connections must be tight and maintained tight so as not to leak air/gas.
CAUTION: Avoid excessive Teflon tape which may inhibit proper
operation.
Each switch is set to vent on rising level at the factory and should
not need field adjustment. For testing the system, we have
provided the red Manual Valve Operator on the operator pilot valve.
3. Valve seat adjustment can be made if air/gas begins to leak. Care should be
taken when adjusting as only slight movement is necessary to stop the
leakage; excessive force will bind the seating mechanism. See the instruction
below for adjustment.