Specifications

Section 20 00-02-2003
06-21-10 - 3 -
4-20mA Output (Analog Option)
Accuracy ± 5% of full scale at 1.5 ips, 100Hz, 21° C (69.8°F)
20 mA corresponds to 1.5 or 3.0 ips peak (factory set)
Alarm Level
Potentiometer for field adjustable alarm level
Alarm level range of 0.1-1.5ips
Alarm Trip Time Delay
Time delay (for actuation) adjustable from 0 to 10 seconds
Output Relay
Normally Open and Normally Closed outputs
Contacts rated 60VDC, 1A and 120VAC, 1A
Isolation Voltage (contacts to signal ground): 500VAC
Latching/non-latching output user selectable
Fail-safe or non-fail-safe operation selected by user
LED Outputs
Solid – Alarm Mode
Solid – Non-Latching mode – LED illuminated if above set point
Blinking – Latching Mode – LED blinks if above set point but not yet alarmed
Solid Green – Always illuminated with power is ON
Reset Input
Activated by external N.O. relay or push button contact
Reset activation time: 0.5 seconds minimum
Reset current < 10mA
Approvals
UL (Pending)
CSA (Pending)
Weight
1.75 lbs (.79 kg)