Specifications

Section 20 00-02-2003
06-21-10 - 14 -
3. If you are setting your vibration alarm as a function of the baseline (or a multiple of the
baseline), first establish the baseline as follows:
Adjust the time delay to the maximum level of 10 seconds.
Use a slotted narrow head screw driver and turn the pot clockwise until the
indicator is pointing to 1.5 IPS.
Starting with the Alarm Setting at the 1.5 IPS, turn the alarm potentiometer
counter clockwise until the Alarm LED begins to flash, thus indicating that the
threshold has been reached. This establishes your alarm baseline.
Rotate the Alarm Potentiometer clockwise to the desired level.
This can be done in Latching or Non-Latching mode.
Measured Alarm Threshold Setup
1. If you need a more accurate setting, use a voltmeter and place the probes on the TP1
test point and TP2 test point.
2. 1 IPS = 1 Volt
3. While reading the voltmeter, adjust the alarm threshold pot to the requirements for your
application.