Specifications
Section 20 00-02-0841
2013-01-14 - 12 -
Pot Settings
The Vibration Setpoint potentiometers (pots) adjust the level detection based on the scale set
in DIP switches 2 through 4. These pots adjust to a percentage of the scale (range) chosen. If
0 to 1.5 IPS is selected as the range, then a pot setting of 50% would cause the EVS-2 to trip
at a vibration of 0.75 IPS. Figures 5 and 6 illustrate these pot settings for the EVS-2.
Figure 5
Figure 6