User`s manual
-3-
1 INTRODUCTION
This new genset controller series consists of two products: Surf-AMF and Surf-Auto. The Surf-AMF monitors
the utility and controls the genset as well as the automatic transfer switch. The Surf-AUTO controls the genset
only. However, the two controllers share many common features. Physically, the Surf has a very attractive and
slim design. It features isolated measurement of the voltages and frequency on the two sources as well as the
current on the load side. It has four user-selectable operating modes: Off, Auto, Utility Only
(1)
or Manual. Front
panel LEDs signal the installation status and operating mode. The user interface consists of an LCD display for
the measurements and faults. The front panel push buttons are provided to select the operating mode and to
access a menu of parameters. The menu gives access to all timers, set points and other parameters relevant to
the control and protection of the installation. The Surf series has a myriad of communication ports: CAN bus,
Serial RS232C, USB, Ethernet and internet. The firmware could be easily upgraded on site via the USB
interface.
2 FEATURES
Microcontroller based design
Automatic mains failure or Auto Start controller
Backlit liquid crystal display (LCD)
Simultaneous display of AC voltage, currents, frequency, hour counter, oil pressure, engine
temperature and battery voltage
Display of power in KW and energy in KWh
Display of fuel consumption rate (L/h), total fuel consumption and RPM (available only if CAN bus is
supported by the engine)
CAN bus J1939 enabled
Ethernet interface
USB interface
Serial RS232S interface
Internet communication: no software installation required
Galvanic isolation for utility and genset AC inputs
Parameters can be edited and updated from any remote interface at any time even when engine is
running
Menu accessible from front panel as well as USB, Ethernet and Serial
Supports communication and SMS via GSM modem
Supports 4-pole systems (Utility and Genset AC inputs are isolated)
Operation by push buttons
Easy to fit DIN standard 196x144 panel mount housing
Connection is via locking plug and socket connectors
Solid-state short circuit protected outputs
Front panel LEDs for inputs status
LCD symbols to display different alarms
Automatic engine starting and stopping
Automatic shutdown on fault condition
Low oil pressure alarm and shut down
High engine temperature alarm and shut down
Dynamo fail alarm and shut down
Low fuel alarm and shut down
Over / Under speed alarm and shut down
Low coolant level alarm and shut down
Over / Under voltage alarm and shut down
Overcurrent alarm and shut down
Configurable I/Os
3 OPERATION
Four modes of operation are provided. Following is a description of each mode:
Off Mode: This mode is entered when the Off push button is pressed for more than 3 seconds. In this
mode, the engine and the module are shut down. All faults and alarms are reset.
1
Only Available for Surf-AMF