User`s manual
-13-
SMS
Alias
Display Parameter Description Range Factory setting
A37 oPS Oil Pressure Sensor type
V1=VDO type 1 (0)
V5=VDO type 2 (1)
MU=Murphy (2)
V1
A38
LoP Low Oil Pressure Pre-alarm N (0), 1 to 255 PSI N
A39 LoA Low Oil Pressure Alarm N (0), 1 to 255 PSI N
A40 ETS Engine Temperature Sensor type
V1=VD0-1 (0)
V2=VD0-2 (1)
MU=Murphy (2)
PT=PT100 (3)
V1
A41
HTP High Engine Temp Pre-alarm N (0), 1 to 255
o
C N
A42 HTA High Engine Temp Alarm N (0), 1 to 255
o
C N
A43 CHT Cooling After High Temperature N (0),Y (1) Y
A44 dcd Dynamo Crank Disconnect N (0), 10 to 26 V 10 V
A45
dSd Dynamo Shut Down N (0), 5 to 10 V 10 V
A46 Hib High Battery N (0), 1 to 255 V 30 V
A47
Hbd High Battery Delay 0 to 255 sec 3 sec
A48 Lob Low Battery N (0), 1 to 255 V 8 V
A49
Lbd Low Battery Delay 0 to 255 sec 2 sec
A50 LcL Low Coolant Level Nc (0), No (1) No
A51 O1 Output 1
N/A=Not Assigned (0)
PRE=Preheat (1)
STA=Starter (2)
EVA= Evalve (3)
C-U=Cont-Utility (4)
C-G=Cont-genset (5)
ALA=Alarm (6)
Cut=Cut Off (7)
PRA=PreAlarm (8)
CG2=Cont-Gstep2 (9)
dLd=Dummy Ld (10)
oLd=Overload (11)
STF=StartFail (12)
AUT=Auto Mode (13)
STA
A52 O2 Output 2 (same as above) EVA
A53 O3 Output 3 (same as above) C-U
A54
O4 Output 4 (same as above) C-G
A55 O5 Output 5 (same as above) ALA
A56
O6 Output 6 (same as above) CG2
A57 RC Remote Control
RoS= Request Genset On
Signal (0)
SUP= Simulate Utility
Present (1)
GRd
A58 I1 Input 1
N/A=Not Assigned (0)
oPS=Oil Pressure (1)
ETS=Engine Temp. (2)
oTS=Oil Temp. (3)
LFo=Low Fuel No (4)
LFc=Low Fuel Nc (5)
LMP=Lamp Test (6)
oPS
A59 I2 Input 2 (same as above) ETS
A60 I3 Input 3 (same as above) oTS
A61
I4 Input 4 (same as above) LFo
A62
I5 Input 5 (same as above) LMP
A63 RHR Run Hour N (0), 1 to 255 hr. 150 hr.
A64 ECU
12
Engine Electronic Control Unit Type
(cannot be modified when engine is
running
)
No=No control unit (0)
SE=Standard engine (1)
VE=Volvo Engine (2)
PE=Perkins Engine (3)
No
A65 APP Accelerator Pedal Position
13
0 to 100 % 50%
A66 IDL Idle Speed Dela
y
13
N (0),1-99 N
12
To enable ECU, boP parameter must be set to Y (ECU cannot be modified when SURF is showing “NotRdy”)
13
These parameters are only available when ECU type is Volvo and cannot be modified when engine is running