PAH-28 Vout, 350-Watt Series
Isolated, 350-Watt, Half-Brick DC-DC Converters
MDC_PAH-28Vout-350W.B05 Page 1 of 21
www.murata-ps.com
www.murata-ps.com/support
For full details go to
www.murata-ps.com/rohs
For applications requiring improved electrical and
thermal performance, consider Murata’s new PAH
series “Half Brick” DC-DC power converters. These
compact modules measure 2.3" X 2.4" X 0.5" (58
X 61 X 12.7mm) and offer the industry-standard
Half Brick footprint.
The PAH Series is ideal for power amplifi er
applications, wireless networks, and telecom
applications. The baseplate provides a means for
conduction cooling in demanding thermal environ-
ment conditions.
The module provides a 28Vdc output at 12.5 Amps
and accepts a wide input voltage range of 18-36 or
36-75 Vdc. The PAH topology offers high effi ciency
(up to 93%), tight line and load regulation, low ripple/
noise, and a fast dynamic load response. A single-
board, highly optimized thermal design contributes to
the superior thermal performance.
These half-bricks provide output trim, sense
pins, and primary side on/off control. Standard fea-
tures also include input under-voltage shutdown,
output over-voltage protection, output short-circuit/
current limiting protection, and thermal shutdown.
PRODUCT OVERVIEW
Typical unit
Typical topology is shown. Some models may vary slightly.
FEATURES
28Vout @ 12.5A (350W)
Trimmable 16.8 Vout to 32.2 Vout @ 350W
with Vin = 18-36V (D24) or 36-75V (D48)
Industry Standard “Half Brick” package
High Effi ciency: up to 93%
Outstanding thermal performance
Standard baseplate for conduction cooled
applications
No output reverse conduction
Input to Output Isolation, 2250Vdc (Basic)
Input under-voltage lockout
On/Off Control (Positive or Negative Logic)
Output over-voltage protection
Thermal shutdown
Output short circuit protection (hiccup
technique)
Certifi ed to UL/EN 60950-1, CSA-C22.2 No.
60950-1, 2nd edition safety approvals
Figure 1. Simplifi ed Schematic
Typical unit
F1
External
DC
Power
Source
Reference and
Error Amplifier
-Vout
Cout
+Vout
Trim
On/Off
Control
-Vin
Open = On
+Vin
logic)
Controller
and Power
Barrier
Case ground
NOTE: A minimum of 470µF
of capacitance is required
on the output to ensure
stable operation. An ESR
equal to or less than 0.02
is also required.
Output (V) Current (A) Input Voltage (V)
28 12.5 18-36 or 36-75