Datasheet

MTU2 Series
Isolated 2W Single & Dual Output SM DC/DC Converters
KDC_MTU2.C02 Page 2 of 9
www.murata-ps.com/support
TEMPERATURE CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Specification All output types -40 85
°C
Storage -50 125
Case temperature rise above ambient
1
0305, 1205, 2405 30 45
All other variants
25 35
Cooling Free air convection
1 . Measured after 1 hour continuous operation at nominal VIN full load at the center of each PCB.
TECHNICAL NOTES
ISOLATION VOLTAGE
‘Hi Pot Test’, ‘Flash Tested’, ‘Withstand Voltage’, ‘Proof Voltage’, ‘Dielectric Withstand Volt-
age’ & ‘Isolation Test Voltage’ are all terms that relate to the same thing, a test voltage,
applied for a specified time, across a component designed to provide electrical isolation,
to verify the integrity of that isolation.
Murata Power Solutions MTU2 series of DC/DC converters are all 100% production tested
at their stated isolation voltage. This is 1kVDC for 1 second.
A question commonly asked is, “What is the continuous voltage that can be applied
across the part in normal operation?”
The MTU2 has been recognized by Underwriters Laboratory for functional insulation, both
input and output should normally be maintained within SELV limits i.e. less than 42.4V
peak, or 60VDC. The isolation test voltage represents a measure of immunity to transient
voltages and the part should never be used as an element of a safety isolation system.
The part could be expected to function correctly with several hundred volts offset applied
continuously across the isolation barrier; but then the circuitry on both sides of the bar-
rier must be regarded as operating at an unsafe voltage and further isolation/insulation
systems must form a barrier between these circuits and any user-accessible circuitry
according to safety standard requirements.
REPEATED HIGH-VOLTAGE ISOLATION TESTING
It is well known that repeated high-voltage isolation testing of a barrier component can
actually degrade isolation capability, to a lesser or greater degree depending on materi-
als, construction and environment. The MTU2 series has toroidal isolation transformers,
with no additional insulation between primary and secondary windings of enameled
wire. While parts can be expected to withstand several times the stated test voltage,
the isolation capability does depend on the wire insulation. Any material, including this
enamel (typically polyurethane) is susceptible to eventual chemical degradation when
subject to very high applied voltages thus implying that the number of tests should be
strictly limited. We therefore strongly advise against repeated high voltage isolation test-
ing, but if it is absolutely required, that the voltage be reduced by 20% from specified
test voltage.
This consideration equally applies to agency recognized parts rated for better than func-
tional isolation where the wire enamel insulation is always supplemented by a further
insulation system of physical spacing or barriers.
SAFETY APPROVAL
The MTU2 series has been recognized by Underwriters Laboratory (UL) to UL 60950 for functional insulation to a maximum product PCB temperature of 120°C. Forced air cooling
may be used to maintain this temperature requirement. File number E151252 applies.
The MTU2 Series of converters are not internally fused so to meet the requirements of UL 60950 an anti-surge input line fuse should always be used with ratings as defined below.
MTU2S03xxxC: 1.5A
MTU2S05xxxC: 0.63A
MTU2S12xxxC: 0.3A
MTU2S24xxxC: 0.25A
All fuses should be UL approved and rated to at least the maximum allowable DC input voltage.